更新時間:Thu Nov 21 01:00:10 CST 2024
產品內容
黃頁詢價
*Head mount
*Programmable for various input signals and measuring range
*Configurable without Power Connected
Inputs:
*Resistance thermometer (PT100)
*Thermocouple (J,K,T,E,B,R,S,N,C)
*mV transmitter
Output:
*2-wire loop-power technology, 4 to 20 mA analog output
*Fault signal on sensor break presettable
Specification
Input
Thermocouple (T/C) :
industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100 : Excitation 180uA. 2 or 3 wire connection (ITS-90 α =0.00385).
Voltage : -60mVdc to 60mVdc.
Accuracy
Refer to Table 1 Input Signal
A/D Resolution
16 bits
Input Sampling Rate
<200 ms
Power Supply
DC 10 to 36V
Max. Load
(V-10) / 0.02 ( Ω )
Output Resolution
0.6 μ A(15 bits)
Output Response Time
<200 ms
Common Mode Rejection Ratio
(CMRR)
>80 dB
Electromagnetic Compatibility
En 50081-2, En 50082-2
Operating Temperature
-10 to 50°C
Humidity
0 to 90% RH
Table 1 Input Signal
Input signal
Maximum Range
Accuracy
Thermocouple J
-50 to 1000°C (-58 to 1832°F)
± 1°C
Thermocouple K
-50 to 1370°C (-58 to 2498°F)
± 1°C
Thermocouple T
-270 to 400°C (-454 to 752°F)
± 1°C
Thermocouple E
-50 to 700°C (-58 to 1292°F)
± 1°C
Thermocouple B
0 to 1750°C (32 to 3182°F)
± 2°C (Note1)
Thermocouple R
-50 to 1750°C (-58 to 3182°F)
± 2°C
Thermocouple S
-50 to 1750°C (-58 to 3182°F)
± 2°C
Thermocouple N
-50 to 1300°C (-58 to 2372°F)
± 2°C
Thermocouple C
-50 to 1800°C (-58 to 3272°F)
± 2°C
Pt100
-200 to 600°C (-328 to 1112°F)
± 0.2°C
mV
-60mV to 60mV
± 0.01mV
Note 1: Accuracy is not guaranteed between 0 and 400°C (0 and 752°F) for type B
Loop Power Signal Transmitter
Model
Type
Input
Output
Isolated
T/C
PT100
mV
mA
V
IST-H
Head Mount
V
V
V
X
X
4-20mA
V
IST-D
DIN Rail
V
V
V
V
V
4-20mA
V
IST-P
Head Mount
0-60KΩ
4-20mA
V
NST
Head Mount
V
V
V
X
X
4-20mA
X